Type MCCB Metasol Molded Case Breakers AB Type
ABS100_b ABS120_b
Frame Size 1000AF 1200AF
Number of Pole 3P, 4P [3]
Rated current [In] 1000A [1000A] 1200A [1200A]
Breaking capacity [Icu] 65kA
Rated operational voltage [Ue] AC: 600V
Rated insulation voltage [Ui] 690V
Type of trip unit Thermal-magnetic
Magnetic trip range 3~6×In …â‘ 
Endurance Mechanical 2,500 operations
Electrical 500 operations
Mount Screw fixing
Size (H,W,D) 3P 400x220x105 mm
Terminal Cable Lug type, Busbar
Dimension